Typical Characteristics of product range
Available for hazardous area applications – Zone 1 & 2
Maximum Application Temperature to 200C
Maximum Circuit length – 15000m
These cables are provided as flexible, cut - to - length. The whole design of the cable relies on insulated conductors which are wired in series (for single phase supplies) or connected in a star connection at the remote end (for three phase supplies).
The cables can be in a variation of a single conductor per cable, two conductors, or three conductors per cable.
SWA – Freeze Protection and Temperature Maintenance |
||||
Cable Type |
Cable Output |
Max Withstand Temp (Power Off) |
Max Energised Temp (Power On) |
Hazardous Area |
FEP single core |
To 60 w/m |
250°C |
200°C |
T1 – T6* |
FEP twin core |
To 60 w/m |
250°C |
200°C |
T1 – T6* |
FEP three core |
To 60 w/m |
250°C |
200°C |
T1 – T6* |
*T ratings are determined as a function of cable output and pipe temperature.