Typical Characteristics of product range
Available for hazardous area applications – Zone 1 & 2
Maximum Application Temperature to 250C
Maximum Circuit length – 200m
Cut to Length
Cable can be crossed on itself without potential over-temperature damage.
These types of cables are very popular due to their inherent safety and cut to length ability.
The general construction is that there are two conductors (bus-wires) providing a live and neutral supply along the length of the cable. A semi conductive heating matrix is extruded between these conductors forming the heating element.
Suitable electrical insulation is further extruded over the matrix providing the dielectric barrier.
The cable is then completed with options of a metallic braid and a further outer jacket for both mechanical and corrosion protection.
The function of the inner conductive core is to generate heat. The output will vary dependant on its temperature and the local environment. This is the self-regulating effect.
The advantage of the cable is that it cannot overheat and can be cut to the desired length. A potential disadvantage is the start-up currents which must be assessed and accounted for with any associated switch gear, thermostats or protection.
Our Range Includes:
SSR – Freeze Protection – Internal Pipe Heating |
|
Output Wattage range (w/m) @ 5C |
10, 15, 25,30 |
Maximum maintain temperature ( energized) |
65°C |
Maximum exposure temperature (de energized) |
85°C |
Minimum installation temperature |
-40°C |
Working voltage range |
110V- 120V / 220-240V |
WSR – Freeze Protection – Industrial / Commercial |
|
Output Wattage range (w/m) @ 5C |
10,17,25,31,40 |
Maximum maintain temperature ( energized) |
65°C |
Maximum exposure temperature (de energized) |
85°C |
Minimum installation temperature |
-40°C |
Working voltage range |
110V- 120V / 220-240V |
HSR – Process Heating – Industrial / Commercial |
|
Output Wattage range (w/m) @ 5C |
35,45,60 |
Maximum maintain temperature (energized) |
110°C |
Maximum exposure temperature (de energized) |
150°C |
Minimum installation temperature |
-40°C |
Working voltage range |
110V- 120V / 220-240V |
H2oSR – Hot Water Temperature Maintenance |
|
Output Wattage range (w/m) @ 5C |
10@55C 10@70C |
Maximum maintain temperature (energized) |
90°C |
Maximum exposure temperature (de energized) |
120°C |
Minimum installation temperature |
-40°C |
Working voltage range |
110V- 120V / 220-240V |
RSR – Roof and Gutter Winter Protection |
|
Output Wattage range (w/m) @ 5C |
25,45,60 |
Maximum maintain temperature (energized) |
110°C |
Maximum exposure temperature (de energized) |
150°C |
Minimum installation temperature |
-40°C |
Working voltage range |
110V- 120V / 220-240V |